- Over-load Protection
- Phase Failure Protection
- Temperature Compensation
- Manual reset
- Automatic reset
- Stop Button
- Test Button
| Temperature Compensation | -10℃~+55℃ |
| Trip Class | CDR6i-25、38:10A CDR6i-93:10 |
| Rated Thermal Current Ui V | 690V |
| Auxiliary Circuit | |||
| Usage Type | AC-15 | DC-13 | |
| Rated Frequency(Hz) | 50 | 50 | 50 |
| Rated Thermal Current Ui(V) | 500 | 500 | 500 |
| Rated operating voltage Ue(V) | 220 | 380 | 220 |
| Rated operating current le (A) | 1.64 | 0.95 | 0.15 |
| Resistive current lth(A) | 5 | 5 | 5 |
| Certification | CCC、CE | ||
| No. | Mulriple of Setting Current | Tripping Time | Initial Condition | Ambient Temperature | |
| Trip class 10A | Trip class 10 | ||||
| Tripping Characteristics for Current Balance | |||||
| 1 | 1.05 | Non-tripping within 2h | Non-tripping within 2h | Non-tripping within 2h | +20°C |
| 2 | 1.2 | Tripping within 2h | Tripping within 2h | Tripping within 2h | |
| 3 | 1.5 | <2min | <4min | <4min | |
| 4 | 7.2 | 2s<Tp≤10s | 4s<Tp≤10s | 4s<Tp≤10s | 4s<Tp≤10s |
| Tripping Characteristics for Current Imbalance | |||||
| Any 2-Phase, 3rd Phase | |||||
| 1 | 1.0 0.9 | Non-tripping within 2h | Non-tripping within 2h | Without previous load | +20°C |
| 2 | 1.15 0 | Tripping within 2h | Tripping within 2h | After No.1 Test | |


