- Small volume saving installation space rated current 125A only 18mm width, saving space by 30%
- Clear Contact indication window position visualization, avoiding incorrect operation
- Better reliable performance temperature rise ≤ 50K, breaking capacity up to 6kA, electric life ≥ 4000 times
- Lighter operating force 125A has lighter operating force, which is convenient for product operation
- Strong environmental adaptability and reliable operation in extreme environment - 35 ℃ ~ 70 ℃ ambient temperature range
- High quality, innovative technology, strict testing, lean production and improve efficiency <EU ROHS Directive> shall be strictly implemented in all stages of design, production, inspection and testing.
Rated voltage | 230V(1P), 400V(2P,3P,4P) |
Rated current | Frame 63: 6A 10A 16A 20A 25A 32A 40A 50A 63A |
Frame 125: 80A 100A 125A | |
Pole | 1P 2P 3P 4P |
Tripping curve | C(5~10In), D(10~16In) |
Rated breaking capacity | 6000A |
Mechanical life | 4000times |
Rated current | Sectional area of conductor(mm²) | Rated current | Sectional area of conductor(mm²) |
6A | 1.0 | 40~50A | 10 |
10A | 1.5 | 63A | 16 |
16~20A | 2.5 | 80A | 25 |
25A | 4 | 100A | 35 |
32A | 6 | 125A | 50 |