frame current | CDM3-63 | CDM3-100 | CDM3-125 | CDM3-160 | |||||||||
Rated voltage Ue(V) | 400/415 | 400/415/690 | 400/415/690 | 400/415/690 | |||||||||
Rated insulation voltage Ui(V) | 800 | 800 | 800 | 800 | |||||||||
Rated impulse withstand voltage Uimp(kV) | 8 | 8 | 8 | 8 | |||||||||
Rated current In(A) | 10-63 | 10-100 | 16-100 | 10-125 | 40-125 | 100-160 | |||||||
Pole (3P,4P-A/B) | 3/4 | 3/4 | 3 | 3/4 | 3/4 | 3 | |||||||
C | F | C | F | N | C | L | S | F | N | H | |||
Icu (kA) | 50/60HZ AC 400/415V | 25 | 50 | 25 | 50 | 70 | 25 | 35 | 35 | 50 | 70 | 85 | |
50/60HZ AC 690V | - | - | - | 8 | - | - | 8 | 8 | 8 | - | - | ||
Ics (kA) | 50/60HZ AC 400/415V | 15 | 30 | 15 | 30 | 50 | 15 | 21 | 21 | 30 | 42 | 64 | |
50/60HZ AC 690V | - | - | - | 8 | - | - | 4 | 4 | 8 | - | - | ||
Mechanical life | maintenance | 40000 | 40000 | 40000 | 40000 | ||||||||
No maintenance | 20000 | 20000 | 20000 | 20000 | |||||||||
Electrical life | AC 400 / 415V | 8000 | 8000 | 8000 | 8000 | ||||||||
Protect type | distribution | ■ | ■ | ■ | ■ | ||||||||
Motor | ■ | ■ | ■ | ■ | |||||||||
Tripping | Thermomagnetic | ■ | ■ | ■ | ■ | ||||||||
magnetic | ■ | ■ | ■ | ■ | |||||||||
Installation type | Fixed front plate wiring | ■ | ■ | ■ | ■ | ||||||||
Fixed back plate wiring | ■ | ■ | ■ | ■ | |||||||||
Plug-in front plate wiring | ■ | ■ | ■ | ■ | |||||||||
Plug-in back plate wiring | ■ | ■ | ■ | ■ | |||||||||
drawout | - | - | - | - | |||||||||
Accessories | undervoltage coil | ■ | ■ | ■ | ■ | ||||||||
shunt coil | ■ | ■ | ■ | ■ | |||||||||
alarm contacts | ■ | ■ | ■ | ■ | |||||||||
auxiliary contacts(1NO1NC) | ■ | ■ | ■ | ■ | |||||||||
auxiliary contacts(2NO2NC) | ■ | ■ | ■ | ■ | |||||||||
external terminal | ■ | ■ | ■ | ■ | |||||||||
motor mechanism CD1 | - | - | - | - | |||||||||
AC/DC power CD2 | ■ | ■ | ■ | ■ | |||||||||
Round handle | ■ | ■ | ■ | ■ | |||||||||
Square handle | ■ | ■ | ■ | ■ | |||||||||
Round external handle | ■ | ■ | ■ | ■ | |||||||||
Square external handle | ■ | ■ | ■ | ■ | |||||||||
Phase barrier | ■ | ■ | ■ | ■ | |||||||||
Others | Overload alarm does not trip | - | - | ■ | ■ | - | - | ■ | ■ | ||||
accessory easy installation | ■ | ■ | ■ | ■ | |||||||||
Isolation | ■ | ■ | ■ | ■ | |||||||||
Usage category | A | A | A | A | |||||||||
Certificate | CCC, KEMA | CCC, KEMA | CCC | CCC, KEMA | |||||||||
Dimensions-Fixed front plate wiring W*H*D | 3P (mm) | 75*130*68 | 75*130*68 | 92*150*93.5 | 75*130*68 | 92*150*75.5 | 107*165*76 | 107*165*88 | |||||
4P (mm) | 100*130*68 | 100*130*68 | 122*150*93.5 | 100*130*68 | 122*150*75.5 | 142*165*76 | 142*165*88 | ||||||
weight | Fiexed 3/4P [kg] | 0.78/0.98 | 0.78/0.98 | 1.28/1.63 | 0.78/0.98 | 1.12/1.42 | 1.53/2.03 | 1.53/2.03 |
frame current | CDM3-250 | CDM3-400 | CDM3-630 | CDM3-800 | ||||||||||||
Rated voltage Ue(V) | 400/415/690 | 400/415/690 | 400/415/690 | 400/690 | ||||||||||||
Rated insulation voltage Ui(V) | 800 | 800 | 800 | 800 | ||||||||||||
Rated impulse withstand voltage Uimp(kV) | 8 | 8 | 8 | 8 | ||||||||||||
Rated current In(A) | 100-250 | 200-400 | 400/500/630 | 630-800 | ||||||||||||
Pole (3P,4P-A/B) | 3/4 | 3 | 3/4 | 3 | 3/4 | 3 | 3/4 | 3 | ||||||||
S | F | N | H | F | N | H | R | F | N | H | R | F | N | R | ||
Icu (kA) | 50/60HZ AC 400/415V | 35 | 50 | 70 | 85 | 50 | 70 | 85 | 100 | 50 | 70 | 85 | 100 | 50 | 70 | 100 |
50/60HZ AC 690V | 8 | 8 | - | - | 8 | 10 | - | - | 10 | 10 | - | - | - | 30 | - | |
Ics (kA) | 50/60HZ AC 400/415V | 21 | 30 | 42 | 64 | 30 | 42 | 51 | 75 | 30 | 42 | 51 | 75 | 30 | 40 | 70 |
50/60HZ AC 690V | 4 | 8 | - | - | 5 | 10 | - | - | 10 | 10 | - | - | - | 20 | - | |
Mechanical life | maintenance | 40000 | 20000 | 20000 | 10000 | |||||||||||
No maintenance | 20000 | 10000 | 10000 | 5000 | ||||||||||||
Electrical life | AC 400 / 415V | 8000 | 7500 | 7500 | 2500 | |||||||||||
Protect type | distribution | ■ | ■ | ■ | ■ | |||||||||||
Motor | ■ | ■ | ■ | ■ | ||||||||||||
Tripping | Thermomagnetic | ■ | ■ | ■ | ■ | |||||||||||
magnetic | ■ | ■ | ■ | ■ | ||||||||||||
Installation type | Fixed front plate wiring | ■ | ■ | ■ | ■ | |||||||||||
Fixed back plate wiring | ■ | ■ | ■ | ■ | ||||||||||||
Plug-in front plate wiring | ■ | - | - | - | ||||||||||||
Plug-in back plate wiring | ■ | ■ | ■ | ■ | ||||||||||||
drawout | - | - | - | ■ | ||||||||||||
Accessories | undervoltage coil | ■ | ■ | ■ | ■ | |||||||||||
shunt coil | ■ | ■ | ■ | ■ | ||||||||||||
alarm contacts | ■ | ■ | ■ | ■ | ||||||||||||
auxiliary contacts(1NO1NC) | ■ | ■ | ■ | ■ | ||||||||||||
auxiliary contacts(2NO2NC) | ■ | ■ | ■ | ■ | ||||||||||||
external terminal | ■ | ■ | ■ | ■ | ||||||||||||
motor mechanism CD1 | - | - | - | ■ | ||||||||||||
AC/DC power CD2 | ■ | ■ | ■ | - | ||||||||||||
Round handle | ■ | ■ | ■ | ■ | ||||||||||||
Square handle | ■ | ■ | ■ | ■ | ||||||||||||
Round external handle | ■ | ■ | ■ | ■ | ||||||||||||
Square external handle | ■ | ■ | ■ | ■ | ||||||||||||
Phase barrier | ■ | ■ | ■ | ■ | ||||||||||||
Others | Overload alarm does not trip | - | ■ | ■ | - | - | - | - | ||||||||
accessory easy installation | ■ | ■ | ■ | - | ||||||||||||
Isolation | ■ | ■ | ■ | ■ | ||||||||||||
Usage category | A | A | A | A | ||||||||||||
Certificate | CCC, KEMA | CCC, KEMA | CCC, KEMA | CCC, KEMA | ||||||||||||
Dimensions-Fixed front plate wiring W*H*D | 3P (mm) | 107*165*76 | 107*165*88 | 150*257*107.5 | 150*257*107.5 | 210*280*100 | ||||||||||
4P (mm) | 142*165*76 | 142*165*88 | 198*257*107.5 | 198*257*107.5 | 280*280*100 | |||||||||||
weight | Fiexed 3/4P [kg] | 1.53/2.03 | 1.53/2.03 | 4.60/5.05 | 5.10/6.24 | 7.34/9.68 |